Single-cope PVC -insulated wires for fixed installation
Conductors:
solid from 1 class soft copper wire
Insulation:
PVC type T1
Insulation color:
yellow-green,sulfuric,blue,brown,gray,orange,pink,red,blue,purple,white,green and yellow,two-color combinations of the above colors are possible.
Maximum operating temperature of the conductor during the operation of the wires:
+70 °C
Minimum ambient temperature for permanently laid wires:
-40 °C
Minimum ambient temperature for wiring:
-5 °C
Maximum core temperature during short circuit:
+160 °C
Test voltage during research 50 Hz:
2000 V
Application:
wires are intended for installation inside equipment and in lighting fixtures.For fixed installation in installation pipes or other wire sheaths,including for signaling and control system.
Packaging:
in coils-100m.
For consultation you can contact us by number +38 (067) 556 38 00 or place an order by filling out the form
| Number and nominal cross-section of conductors
(mm2) |
Number of wires in a conductor
(n) |
Nominal insulation thickness
(mm2) |
Estimated outer diameter of the wire
(mm2) |
Estimated drive weight
(kg/km) |
Maximum conductor resistance at
t=+20 °C (Ω/km) |
Maximum insulation resistance at
t=+70 °C |
| 0,5 | 1 | 0.6 | 2,0 | 8 | 36,0 | 0,014 |
| 0.75 | 0.6 | 2.2 | 11 | 24.5 | 0,5 | 0.013 |
| 1.0 | 1 | 0.7 | 2,6 | 14 | 18,1 | 0,011 |
| 1,5 | 1 | 0.7 | 2,8 | 20 | 12,1 | 0,011 |
| 2,5 | 1 | 0,8 | 3,3 | 31 | 7,41 | 0,010 |
| 4,0 | 1 | 0,8 | 3,8 | 45 | 4,61 | 0,0087 |
| 6.0 | 1 | 0,8 | 4.3 | 64 | 3.08 | 0.0074 |
| 10.0 | 1 | 1.0 | 5.5 | 107 | 1.83 | 0.0072 |
And we will keep you informed of all the events of our company