Electric power cables for fixed installation, with single-wire copper conductors, with PVC insulation and sheath, flat.
Conductors:
solid copper class 1
Insulation:
PVC
Insulation color:
white,black and others.
Maximum operating temperature of the conductor during the operation of the wires:
+70 °C
Application:
for stationary installation in electric power equipment in dry and damp rooms on plaster and under plaster
Packaging:
in coils-100m.
For consultation you can contact us by number +38 (067) 556 38 00 or place an order by filling out the form
| Number and nominal cross-section of conductors
(n x mm2) |
The number of wires in the conductor | Nominal insulation thickness
(mm) |
Nominal sheath
thickness (mm) |
Maximum external dimensions of the wire
(mm) |
Maximum conductor resistance at
t=+20 °C (Ω/km) |
Minimum insulation resistance at
t=+70 °C (MΩ/km) |
Estimated weight of a wire 1 km long
(kg/km) |
Nominal length of wire segments
(m) |
| 2×1 | 1 | 0.8 | 1.2 | 6.1×9.2 | 18.1 | 0.014 | 62 | 200 |
| 2×1.5 | 1 | 0.8 | 1.2 | 6.3×9.6 | 12.1 | 0.012 | 73 | 200 |
| 2×2.5 | 1 | 0.8 | 1.2 | 6.7×10.4 | 7.41 | 0.010 | 97 | 200 |
| 2×4 | 1 | 0.9 | 1.2 | 7.4×11.8 | 4.61 | 0.0093 | 135 | 100 |
| 3×1 | 1 | 0.8 | 1.2 | 6.1×12.3 | 18.1 | 0.014 | 87 | 200 |
| 3×1.5 | 1 | 0.8 | 1.2 | 6.3×12.9 | 12.1 | 0.012 | 104 | 200 |
| 3×2.5 | 1 | 0.8 | 1.2 | 6.7×14.1 | 7.41 | 0.010 | 140 | 200 |
| 3×4 | 1 | 0.9 | 1.2 | 7.4×16.2 | 4.61 | 0.0093 | 196 | 100 |
And we will keep you informed of all the events of our company